Cooling Water Test kit RXSOL 309 manufacturer supplier distributor in Mumbai, Kandla, Kolkata, Vizag, Chennai, India, Fujairah, Dubai UAE, Muscat Oman, Kenya Africa. Get the best quality of Cooling Water Test kit RXSOL 309 at a competitive price from us. We have ready stock of Cooling Water Test kit RXSOL 309 in India, UAE Gulf, Oman, Kenya Africa. Contact us for bulk as well as small orders.


MUSCAT CHEMICAL TAG::

REAGENT:-NITRITE, CHLORIDE , pH, ALKALINITY

Remarks

Note


Procdure:-

NITRITE PROCEDURE for test ( STEP WISE ):

  1. Measure 1 ml of SAMPLE WATER in graduated TEST TUBE / CYLINDER , with the help of syringe / pippet and diluted with Distilled Water up to 10 ml.
  2. Add 1-2 drops of  RXSOL TK5 and mix with the stirring rod , to obtain ORANGE / light reddish  colour. 
  3. Add RXSOL TK6  drop by drop , mixing with the stirring rod until  For endpoint ORANGE to BLUE / GREENISH colour just appears / develop. 
     

Each DROPS is equivalent to 50 PPM of NO2

CALCULATION :-50 X Number of DROPS of TK6

CHLORIDE PROCEDURE for test ( STEP WISE ):-

  1. Measure 15 ml of SAMPLE WATER in graduated TEST TUBE / CYLINDER
  2. Add 1-2 drops of  RXSOL TK1 and mix with the stirring rod , If  sample turns red / PINK then follows 3rd step otherwise if sample remains colourless proceed to step 4.
  3. Add RXSOL TK2  drop by drop , mixing with the stirring rod until colour just disappears.
  4. Add 3 drops of RXSOL TK3 and mix with stirring rod , the sample will turn YELLOW.
  5. AddRXSOL TK4 carefully by counting drop by drop and mixing throughly until a light reddish / pink / brown colour develop.

RESULT :- Each DROPS is equivalent to 8 PPM of CHLORIDES .

PROCEDURE for TOTAL ALKALINITY:-

Measure 10 ml of SAMPLE WATER in graduated TEST TUBE / CYLINDER

Add 1-2 drops of  RXSOL TK7 and mix with the stirring rod , If  sample turns red / PINK ( which indicates presence of p-Alkalinity ) then follows 3rd step otherwise if sample remains colourless ( Record p-Alkalinity = 0 ) then proceed to STEP- 4.

Add RXSOL TK9  drop by drop ( by counting ) , mixing with the stirring rod until colour just disappears. Each drop is equivalent to 15 ppm of p-Alkalinity , expressed as CaCO3

Add 2-3 drops of RXSOL TK8 and mix with stirring rod , the sample will turn to BLUISH-GREEN .

AddRXSOL TK9 carefully by counting drop by drop and mixing throughly until a light reddish ( salmon ) pink  colour develop.

RESULT:-Each DROPS is equivalent to 25 PPM of Alkalinity