Product Dose
- 8022043 reads
For optimum results dose Hardness Control direct to the boiler via the bypass pot-feeder. The dry powder should be dissolved in hot water (50°C) at a ratio of 1 part powder to twenty parts condensate (e.g. 500 grams/10 litres). Ensure that treatment is fully dissolved before dosing.
Dosage and control
Phophate test result in pPM PO4 |
|||||||
Pressure |
0 - 10 |
10 - 20 |
20 - 30 |
30 - 40 |
40 - 50 |
> 50 |
Control range |
0-40 Bar |
23 |
11.5 |
Satisfactory |
Satisfactory |
Blow Down |
20-50 |
|
41-60 Bar |
17 |
5.5 |
Satisfactory |
Blow Down |
Blow Down |
15-30 |
|
> 60 Bar |
5.5 |
Satisfactory |
Satisfactory |
Blow Down |
Blow Down |
10-25 |
Select row on righthand side for applicable pressure range. Compare test result with comment in table and dose stated amount of product per ton boiler water volume.
These are recommended values based on experience and are in no way intended to replace the boiler manufacturer's specifications or company regulations.
Hardness Control is formulated to form a precipitate with calcium ions which will not adhere to metal surfaces but are in a form suitable for blowdown.
Benefit and Features
- Highly active phosphate based compound, economical in use.
- Easily dissolved in water for dosing.
- Scale problems due to calcium are eliminated.
- Maintains sludge in a non-adherent state for ease of blow down.
- Simple test to determine level of treatment.
-
Can be used for boilers of all pressures.
Rxsol Hardness Control does not influence the alkalinity in the system