Grease and
Application : RXSOL-50-5004-020 is strongly alkaline. It is best applied diluted with WATER , any convenient strength on a continuous basis using a suitable chemicals pump . The product should be applied to the boiler feed tank or feed line to ensure adequate mixing.
Dose : The dose rate is dependent on boiler operating condition . Feed 200 gm to 1 Kg of RXSOLComoTreat solution per thousand Ltrs of boilers water. Then control the system by Periodic Alkalinity test procedure. If p-Alkalinity is below 200 ppm increase the ratio of RXSOLComoTreat solution. If p-Alkalinity is above 400 ppm reduce the concentration of RXSOLComoTreat solution by dilution with water. Benefits : RXSOL ALKALINITY, PHOSPHTE and SULFITE TEST KITS are available on request.
Usage Procedure : Always dissolve powder before feeding in BOILER WATER TANK.
Control Procedure :Control is by simple boiler water tests or RX CLEANSERS can provide a suitable test kits for this purpose.
FREE LOGSHEET is available for our registered member. ( Maintaining of Logsheet allow to observing and evaluating the test results trend in order to use the exact amount needed for the stabilization of the system
|